
Page 59 of 66
©Retrotec Inc. 2012
Cannot Reach 25 Pa Factors
Take CFM reading at pressure achieved and multiply by "Cannot reach 25 Pa factor" to get pressure at
50 Pa. e.g. read 600 CFM at building pressure of 19 Pa. Factor is 1.18,
600 x 1.18 = 708 CFM
Table 11. Factors for when a building pressure of 25 Pa cannot be reached (“n” value of 0.6).
Comentários a estes Manuais